Learning Content and Theses

Platform for digital learning at HSHL

Three-Phase Power

Electrical power is defined as the product of voltage and current. First we look at these quantities in the time domain.

Power in the time domain

In the time domain, the following applies to sinusoidal voltages and currents:

\[ \begin{gathered} i(t) = \hat{\imath} \cdot \sin(\omega t + \varphi_i) \\[4pt] u(t) = \hat{u} \cdot \sin(\omega t + \varphi_u) \\[4pt] p(t) = u(t) \cdot i(t) \end{gathered} \]

Let us first consider only the (single-phase) alternating current from the fundamentals of electrical engineering, not three-phase current. Active power P is generated when voltage and current are in phase, i.e. when φu = φi. In the simplest case, both phase angles are 0. Let us look at the resulting power graphically:

Time waveforms of u(t), i(t) and p(t) for active power: the power pulsates between 0 and the peak value
\[ \begin{gathered} \text{Example values of the waveforms above:} \\[2pt] i(t) = 1\,\mathrm{A} \cdot \sin(\omega t + 0) \\[4pt] u(t) = 1\,\mathrm{V} \cdot \sin(\omega t + 0) \\[4pt] p(t) = 1\,\mathrm{W} \cdot \sin^2(\omega t) = \frac{1}{2}\,\mathrm{W} - \frac{1}{2}\,\mathrm{W} \cdot \cos(2\omega t) \end{gathered} \]

In this special case, voltage (blue) and current (red) are in phase; they are not shifted in time relative to each other. I have shifted them very slightly against each other only for the graph, so that both curves are visible. The product of u(t) and i(t) is then always positive. The power (green), however, pulsates over time; it is not constant. If such a power is drawn from a generator, the generator shaft is loaded mechanically unevenly. That is not good. We want a continuous electrical power over time.

The solution lies in a 3-phase system. Because voltage and current are each shifted by 120°, the power in a three-phase system is also shifted by 120° in each case. In the figure below, I have drawn the power of the single-phase system above three times, each with a 120° phase shift.

Powers p1(t), p2(t), p3(t) of the three phases and their constant sum of 1.5 W
\[ \begin{gathered} p_1(t) = 0.5\,\mathrm{W} - 0.5\,\mathrm{W} \cdot \cos(2\omega t) \\[4pt] p_2(t) = 0.5\,\mathrm{W} - 0.5\,\mathrm{W} \cdot \cos(2\omega t - 120^\circ) \\[4pt] p_3(t) = 0.5\,\mathrm{W} - 0.5\,\mathrm{W} \cdot \cos(2\omega t + 120^\circ) \\[4pt] p_1(t) + p_2(t) + p_3(t) = 1.5\,\mathrm{W} \\[4pt] \hat{p} = 0.5\,\mathrm{W} \\[4pt] \sum p_i(t) = 3 \cdot \hat{p} \end{gathered} \]

In this example, each of the powers lies in the range [0W … 1W]. This value of course depends on the load and is not always the same. Pure active power always lies in the range 0W to XW. The frequency of the power is twice that of voltage and current. The sum of the powers is – and this is what matters here – constant at every point in time. You can check this at simple points in time:

At t = 0 ms, the sum of the three powers is 0W + 0.75W + 0.75W = 1.5W.

At t = 5 ms, the sum of the three powers is 1W+0.25W+0.25W = 1.5W.

In symmetrical systems, the following applies at every point in time:

\[ \begin{gathered} \text{Three-phase current: } i_1(t) + i_2(t) + i_3(t) = 0\,\mathrm{A} \\[4pt] \text{Three-phase voltage: } u_1(t) + u_2(t) + u_3(t) = 0\,\mathrm{V} \\[4pt] \text{Three-phase power: } p_1(t) + p_2(t) + p_3(t) = 3 \cdot \hat{p} \end{gathered} \]

The sum of the powers is not 0, because the sine waves do not lie around 0. The waveforms of the powers are shifted upwards.

In a three-phase system we have achieved that a generator is continuously loaded with the same constant mechanical power. The generator shaft does not care which electromagnet is exerting which individual force at any moment, as long as the total force of all three electromagnets is constant over time.

Complex apparent power

So far we have only considered active power at resistors in the time domain. From now on we work only in the frequency domain with complex RMS phasors. With active power, voltage and current are in phase. Consumers with complex impedances generally need apparent power. For this we need voltage and current at a load.

The three-phase voltage of the grid is always fixed. The current results from the load.

\[ \begin{gathered} \text{Three-phase voltage system in star connection with RMS phasors:} \\[2pt] U_1 = 230\,\mathrm{V} \cdot e^{j0} \\[4pt] U_2 = 230\,\mathrm{V} \cdot e^{-j\frac{2}{3}\pi} \\[4pt] U_3 = 230\,\mathrm{V} \cdot e^{j\frac{2}{3}\pi} \end{gathered} \]

\[ \begin{gathered} \text{Example:} \\[2pt] \text{Symmetrical impedance } Z_1 = Z_2 = Z_3 = Z_{\mathrm{Last}} \\[4pt] Z_{\mathrm{Last}} = j\omega L = j10\,\Omega = 10\,\Omega \cdot e^{j\frac{\pi}{2}} \\[6pt] I_1 = \frac{U_1}{Z_{\mathrm{Last}}} = \frac{230\,\mathrm{V} \cdot e^{j0}}{10\,\Omega \cdot e^{j\frac{\pi}{2}}} = 23\,\mathrm{A} \cdot e^{-j\frac{\pi}{2}} \\[6pt] I_2 = \frac{U_2}{Z_{\mathrm{Last}}} = \frac{230\,\mathrm{V} \cdot e^{-j\frac{2}{3}\pi}}{10\,\Omega \cdot e^{j\frac{\pi}{2}}} = 23\,\mathrm{A} \cdot e^{-j\frac{2}{3}\pi - j\frac{\pi}{2}} = 23\,\mathrm{A} \cdot e^{-j\frac{7\pi}{6}} \\[6pt] I_3 = \frac{U_3}{Z_{\mathrm{Last}}} = \frac{230\,\mathrm{V} \cdot e^{j\frac{2}{3}\pi}}{10\,\Omega \cdot e^{j\frac{\pi}{2}}} = 23\,\mathrm{A} \cdot e^{j\frac{2}{3}\pi - j\frac{\pi}{2}} = 23\,\mathrm{A} \cdot e^{j\frac{\pi}{6}} \\[8pt] \text{General apparent power: } S = U \cdot I^{\textcolor{#c00000}{*}} \\[4pt] \text{Example:} \\[2pt] S_1 = U_1 \cdot I_1^* = 230\,\mathrm{V} \cdot e^{j0} \cdot 23\,\mathrm{A} \cdot e^{\textcolor{#c00000}{+}j\frac{\pi}{2}} = 5.3\,\mathrm{kVA} \cdot e^{j\frac{\pi}{2}} = j5.3\,\mathrm{kVA} \\[4pt] S_2 = U_2 \cdot I_2^* = 230\,\mathrm{V} \cdot e^{-j\frac{2}{3}\pi} \cdot 23\,\mathrm{A} \cdot e^{\textcolor{#c00000}{+}j\frac{7\pi}{6}} = 5.3\,\mathrm{kVA} \cdot e^{j\frac{\pi}{2}} = j5.3\,\mathrm{kVA} \\[4pt] S_3 = U_3 \cdot I_3^* = 230\,\mathrm{V} \cdot e^{j\frac{2}{3}\pi} \cdot 23\,\mathrm{A} \cdot e^{\textcolor{#c00000}{-}j\frac{\pi}{6}} = 5.3\,\mathrm{kVA} \cdot e^{j\frac{\pi}{2}} = j5.3\,\mathrm{kVA} \\[6pt] Q_1 = \mathrm{Im}\{S_1\} = 5.3\,\mathrm{kvar} \\[4pt] Q_2 = \mathrm{Im}\{S_2\} = 5.3\,\mathrm{kvar} \\[4pt] Q_3 = \mathrm{Im}\{S_3\} = 5.3\,\mathrm{kvar} \end{gathered} \]

The apparent power is the same in every phase. What is interesting is that the phase of the apparent power is the same in every phase, even though the phases of voltage and current differ between the phases. The apparent power only indicates the shares of active and reactive power of a consumer. Active and reactive power indicate how voltage and current are phase-shifted relative to each other.

  • No phase shift: only active power
  • 90° phase shift: only reactive power:
  • Otherwise: a mix of both.

The phase shift comes from the consumers or loads, because the voltages are rigid. A consumer shifts the variable phase of the current relative to the phase of “its” voltage. With a symmetrical load, every consumer does this in the same way on every phase. This can be seen best graphically in the phasor diagram.

Phasor diagrams of the voltages U1, U2, U3 and the currents I1, I2, I3 with the phase angles

On the left you see the three-phase voltage system in star connection. On the right you see the current from the example. The voltage is drawn dashed in the right phasor diagram so that we have its directions in the diagram. Otherwise, voltage phasors have no business in a current phasor diagram. The phase between voltage and current is rotated by 90° in all three phases. So the phase angles of the three phases are equal.

The angle φU of the voltage indicates how the voltage is shifted in time relative to a fixed point t = 0s. The angle φI of the current indicates how the current is shifted in time relative to a fixed point t = 0s. The angle φ of the apparent power indicates how voltage and current are shifted relative to each other. The absolute phase positions of U and I play no role here. Only their relative shift matters. And you can see it in the right part of the figure above. All three are equal.

This relationship is very important, so I will explain it again in the time domain in three figures, each showing the voltage and current of one of the three phases:

Voltage u1(t) and current i1(t): the current is shifted to the right by π/2
\[ \begin{gathered} U_1 = 230\,\mathrm{V} \cdot e^{j0};\; \varphi_U = 0 \\[4pt] Z_L = j10\,\Omega = 10\,\Omega \cdot e^{j\frac{\pi}{2}};\; \varphi_Z = \frac{\pi}{2} \\[4pt] I_1 = \frac{U_1}{Z} = \frac{230\,\mathrm{V} \cdot e^{j0}}{10\,\Omega \cdot e^{j\frac{\pi}{2}}} = 23\,\mathrm{A} \cdot e^{-j\frac{\pi}{2}};\; \varphi_I = -\frac{\pi}{2} \\[4pt] \varphi_1 = \varphi_U - \varphi_I = 0 - \left(-\frac{\pi}{2}\right) = \frac{\pi}{2} \end{gathered} \]
Voltage u2(t) and current i2(t) with φU = −2/3 π and φI = −7/6 π
\[ \begin{gathered} U_2 = 230\,\mathrm{V} \cdot e^{-j\frac{2}{3}\pi};\; \varphi_U = -\frac{2}{3}\pi \\[4pt] I_2 = \frac{U_2}{Z} = \frac{230\,\mathrm{V} \cdot e^{-j\frac{2}{3}\pi}}{10\,\Omega \cdot e^{j\frac{\pi}{2}}} = 23\,\mathrm{A} \cdot e^{-j\frac{7\pi}{6}};\; \varphi_I = -\frac{7}{6}\pi \\[4pt] \varphi_2 = \varphi_U - \varphi_I = -\frac{2}{3}\pi - \left(-\frac{7}{6}\pi\right) = \frac{\pi}{2} \end{gathered} \]
Voltage u3(t) and current i3(t) with φU = 2/3 π and φI = π/6
\[ \begin{gathered} U_3 = 230\,\mathrm{V} \cdot e^{j\frac{2}{3}\pi};\; \varphi_U = \frac{2}{3}\pi \\[4pt] I_3 = \frac{U_3}{Z} = \frac{230\,\mathrm{V} \cdot e^{j\frac{2}{3}\pi}}{10\,\Omega \cdot e^{j\frac{\pi}{2}}} = 23\,\mathrm{A} \cdot e^{j\frac{\pi}{6}};\; \varphi_I = \frac{\pi}{6} \\[4pt] \varphi_3 = \varphi_U - \varphi_I = \frac{2}{3}\pi - \frac{\pi}{6} = \frac{\pi}{2} \end{gathered} \]

In all three cases the phase angle is the same. The RMS values of voltage and current are also equal in each case, because the load impedance is the same. So the apparent powers are also equal.

Let us calculate the active and reactive powers from this. The following applies

\[ \begin{gathered} S = 5.3\,\mathrm{kVA};\; \varphi = \frac{\pi}{2} \\[4pt] P = S \cdot \cos(\varphi) = 0\,\mathrm{W} \\[4pt] Q = S \cdot \sin(\varphi) = 5.3\,\mathrm{kvar} \\[4pt] S = P + jQ \end{gathered} \]

Download course as PDF

The PDF contains all pages of the course. Interactive content is only available on the website.