Summary: Three-Phase Current

For three-phase current, the following applies in general:

In electrical power supply systems it is generally assumed that the three-phase generator (power plant or source) is symmetrical.

Three-phase current is generated, for example, by:

  • synchronous or asynchronous machines in (conventional) power plants
  • converter circuits (power electronics) in converters, “inverters” (advanced lecture on power electronics)

Asymmetrical conditions in three-phase systems arise from the connection of asymmetrical or single- or two-phase consumers/loads

Assuming (almost) ideal voltage sources at the power plant, the line-to-line voltages in a three-phase system then remain symmetrical, but the currents do not

Different RMS voltage values (e.g. approx. 230 V and approx. 400 V) can be used in three-phase systems

  • star voltage 230V, i.e. conductor to N conductor (“earth”)
  • line-to-line voltage 400V, i.e. voltage between two line conductors

To designate (nominal value) a three-phase system, the RMS value of the line-to-line voltage (e.g. 380 kV, 220 kV, 10 kV, 400V) is generally used

The RMS value of a line-to-line voltage (conductor-to-conductor voltage or delta voltage) is larger by a factor of root(3) than that of a star voltage (line-to-earth voltage)

The power specified for a three-phase system always refers to the entire system, i.e. in symmetrical systems 1/3 of the total power is converted per line conductor.

\[ \begin{gathered} \text{Star and delta voltages} \\[2pt] \text{Considering RMS phasors in the grid with: } |U_{LL}| = U\text{:} \end{gathered} \]
Star and delta voltages: time waveforms, RMS phasors and voltages between L1, L2, L3 and N
\[ \begin{gathered} U_1 = \frac{U}{\sqrt{3}} \cdot e^{j0} = \frac{U}{\sqrt{3}} \\[4pt] U_2 = \frac{U}{\sqrt{3}} \cdot e^{j240^\circ} = \frac{U}{\sqrt{3}} \cdot e^{j\frac{4\pi}{3}} = \frac{U}{\sqrt{3}} \cdot \left(-\frac{1}{2} - j\frac{\sqrt{3}}{2}\right) \\[4pt] U_3 = \frac{U}{\sqrt{3}} \cdot e^{j120^\circ} = \frac{U}{\sqrt{3}} \cdot e^{j\frac{2\pi}{3}} = \frac{U}{\sqrt{3}} \cdot \left(-\frac{1}{2} + j\frac{\sqrt{3}}{2}\right) \\[4pt] U_{12} = U \cdot e^{j30^\circ} = U \cdot e^{j\frac{\pi}{6}} = U \cdot \left(\frac{\sqrt{3}}{2} + j\frac{1}{2}\right) \\[4pt] U_{23} = U \cdot e^{j270^\circ} = U \cdot e^{j\frac{3\pi}{2}} = -j \cdot U \\[4pt] U_{31} = U \cdot e^{j150^\circ} = U \cdot e^{j\frac{5\pi}{6}} = U \cdot \left(-\frac{\sqrt{3}}{2} + j\frac{1}{2}\right) \end{gathered} \]
\[ \begin{gathered} |U_1| = |U_2| = |U_3| = \frac{U}{\sqrt{3}} \text{ (always applies)} \\[4pt] \text{Symmetrical load:} \\[2pt] |I_1| = |I_2| = |I_3|;\; |I_0| = 0\,\mathrm{A} \\[4pt] \varphi_1 = \varphi_2 = \varphi_3 = \varphi_{Z,\mathrm{Last}} \\[4pt] S_1 = S_2 = S_3;\; P_1 = P_2 = P_3;\; Q_1 = Q_2 = Q_3 \end{gathered} \]
\[ \text{Load in star connection} \]
Load in star connection: grid with L1, L2, L3, N and load of three impedances Z with the currents I1, I2, I3 and I0
Netz = grid · Last = load
\[ \begin{gathered} I_1 = I_{1\curlywedge};\; I_2 = I_{2\curlywedge};\; I_3 = I_{3\curlywedge} \\[4pt] U_Z = U_{LN};\; |U_{LN}| = \frac{|U_{LL}|}{\sqrt{3}} \\[4pt] I_1 = \frac{U_1}{Z};\; I_2 = \frac{U_2}{Z};\; I_3 = \frac{U_3}{Z} \\[8pt] \text{Power considerations:} \\[2pt] S_1 = U_1 \cdot I_1^*;\; S_2 = U_2 \cdot I_2^*;\; S_3 = U_3 \cdot I_3^* \\[4pt] S_{\mathrm{Ges}} = S_1 + S_2 + S_3 \end{gathered} \]
\[ \text{Load in delta connection} \]
Load in delta connection: grid with L1, L2, L3 and load of three impedances Z between the line conductors
Netz = grid · Last = load
\[ \begin{gathered} I_1 = I_{12\Delta} - I_{31\Delta} \\[4pt] I_2 = I_{23\Delta} - I_{12\Delta} \\[4pt] I_3 = I_{31\Delta} - I_{23\Delta} \\[4pt] U_Z = U_{LL} \\[4pt] I_{12\Delta} = \frac{U_{12}}{Z};\; I_{23\Delta} = \frac{U_{23}}{Z};\; I_{31\Delta} = \frac{U_{31}}{Z} \\[8pt] \text{Power considerations:} \\[2pt] S_1 = U_{12} \cdot I_{12\Delta}^*;\; S_2 = U_{23} \cdot I_{23\Delta}^*;\; S_3 = U_{31} \cdot I_{31\Delta}^* \\[4pt] S_{\mathrm{Ges}} = S_1 + S_2 + S_3 \end{gathered} \]
\[ \begin{gathered} \text{If the same load } Z \text{ is connected once in delta} \\ \text{and once in star:} \\[4pt] U_{\Delta} = U_{LL} \\[4pt] I_{\Delta} = \frac{U_{LL}}{Z} \\[4pt] S_{\Delta} = U_{LL} \cdot I_{\Delta}^* \end{gathered} \]
\[ \begin{gathered} |U_{\curlywedge}| = \frac{|U_{LL}|}{\sqrt{3}} = |U_{LN}| \\[4pt] |I_{\curlywedge}| = \frac{|U_{LN}|}{Z} = \frac{|U_{LL}|}{\sqrt{3} \cdot Z} = \frac{|I_{\Delta}|}{\sqrt{3}} \\[4pt] S_{\curlywedge} = U_{LN} \cdot I_{\curlywedge}^* = \frac{S_{\Delta}}{3} \\[6pt] \text{Magnitudes only,} \\ \text{because the angles change between } \Delta \text{ and } \curlywedge \end{gathered} \]

Advantages of three-phase current

  • Power that is constant over time rather than pulsating
  • Simple generation of three-phase current with three-phase (synchronous) generators
  • Simultaneous use of two voltage levels possible (line-to-line and star voltages)
  • More economical operation for the same power transmission (fewer conductors needed)
  • Direct operation of three-phase motors possible