The voltage in the grid is specified by the power plant. The current depends on the load. Let us assume a passive load consisting of resistors. The voltage is given as a star quantity. The load is connected in star. Then a current IStern flows in the load. In the formulas I use the lambda symbol for this, because it comes quite close to a star.
Last in Sternschaltung \(\curlywedge\) = load in star connection ⅄ · Last = load · Sternschaltung = star connection
In the example above, resistors were used as the load. Of course, you load a three-phase system in the same way with complex loads. Now the same load is connected in delta to the same source:
Last in Dreiecksschaltung \(\Delta\) = load in delta connection Δ · Last = load · Dreiecksschaltung = delta connection
The RMS values of voltage and current at the load are each larger by a factor of root (3) in delta connection than in star connection. That is why the apparent power in delta connection is larger by a factor of 3 than in star connection. Of course, this only applies if the same circuit with the same load impedance is used for the comparison.
In delta connection, the following node rules apply to the current:
The term “phase” (German: Strang) is not unambiguous. It means something different in star connection than in delta connection. This is for historical reasons.
\[
\begin{gathered}
\text{Star connection:} \\[2pt]
\text{Phase: line between } L_X \text{ and } N \\[2pt]
\text{Phase voltage: } U_{LN} \\[2pt]
\text{Phase current: } I_{LN}
\end{gathered}
\]
\[
\begin{gathered}
\text{Delta connection:} \\[2pt]
\text{Phase: line between } L_X \text{ and } L_Y \\[2pt]
\text{Phase voltage: } U_{LL} \\[2pt]
\text{Phase current: } I_{LL}
\end{gathered}
\]
If no reference system is specified in exercises, phase quantities always refer to the quantities defined for the delta connection.