Learning Content and Theses

Platform for digital learning at HSHL

Single-Phase Equivalent Circuit

With a symmetrical load, all three currents behave in the same way. They are only phase-shifted by 120° relative to one another. It therefore makes sense to simplify the calculation by considering only one phase. Of course, this only works with a symmetrical load. We consider the simplification only in star connection, because there we can consider each conductor on its own.

Once we have calculated the power in one phase, the total power is simply three times as high. Once we have calculated the current of one phase, the other two currents have the same magnitude, only phase-shifted. For the simplification we take phase 1, because for U1:

\[ U_1 = \frac{400\,\mathrm{V}}{\sqrt{3}} \text{ with } \varphi_{U1} = 0^\circ \]

So conveniently we have no phase shift in the voltage. That pleases the lazy engineer. The following figure shows on the left the real connection of a symmetrical load of impedance Z to a three-phase voltage system:

Real connection of a symmetrical load Z in star connection (left) and single-phase equivalent circuit with U1, I1 and Z (right)

On the right you see the simplified single-phase equivalent circuit. Three oblique parallel strokes on a line indicate that it is actually a three-phase system. If the system is to be drawn without a return conductor to the star point, please use the following equivalent circuit:

Single-phase equivalent circuit: source U1 drives the current I1 through the load Z, three strokes mark the three-phase system

In many machines the star point of the load is not accessible; it is simply not brought out as a cable. In these cases no return conductor is drawn in the equivalent circuit either.