Learning Content and Theses

Platform for digital learning at HSHL

Reactive Power Compensation from the Current

There is a legal requirement for high-power installations: cos(φ) ≥ 0,95. This requirement protects the grid from too much reactive power. It happens, for example, that too much reactive power is generated at a motor and cos(φ) is too small. Then we need a local compensation network so that the storage elements are recharged locally at the consumer.

For this, we again consider the load from the previous chapter:

Load of three phases R and L in star connection at the grid connection L1, L2, L3, N
Netzanschluss = grid connection · Last = load
\[ \begin{gathered} U_1 = \frac{400\,\mathrm{V}}{\sqrt{3}} \cdot e^{j0} = \frac{400\,\mathrm{V}}{\sqrt{3}} \\[4pt] Z_1 = R + j\omega L = (1 + j)\,\Omega = \sqrt{2} \cdot e^{j\pi/4} \\[4pt] I_1 = I_{1L} = \frac{U_1}{Z_1} = \frac{\frac{400\,\mathrm{V}}{\sqrt{3}}}{\sqrt{2}\,\Omega \cdot e^{j\pi/4}} = 163.3\,\mathrm{A} \cdot e^{-j\pi/4} \\[4pt] \varphi = \varphi_U - \varphi_I = 0 - \left(-\frac{\pi}{4}\right) = \frac{\pi}{4} \\[4pt] \cos(\varphi) = \cos\left(\frac{\pi}{4}\right) = \frac{1}{\sqrt{2}} = 0.71 \ll 0.95 \end{gathered} \]

For reactive power compensation, we build the following capacitive compensation network directly at the grid connection of the load:

Reactive power compensation: three capacitors C in star connection at the grid connection, current I1B into the capacitor
Netzanschluss = grid connection · Blindleistungs-Kompensation = reactive power compensation

Only (capacitive) reactive current flows into a capacitor. This is current that is shifted by a positive phase angle relative to the voltage. For the phase between voltage and current:

Capacitors C of the reactive power compensation at the grid connection with the current I1B
Netzanschluss = grid connection · Blindleistungs-Kompensation = reactive power compensation
\[ \begin{gathered} U_1 = \frac{400\,\mathrm{V}}{\sqrt{3}} \cdot e^{j0} = \frac{400\,\mathrm{V}}{\sqrt{3}} \\[4pt] Z_C = \frac{1}{j\omega C} = -j\frac{1}{\omega C} = \frac{1}{\omega C} \cdot e^{-\frac{j\pi}{2}};\; \varphi_Z = -\frac{\pi}{2} \\[4pt] I_1 = I_{1B} = \frac{U_1}{Z_C} = \frac{\frac{400\,\mathrm{V}}{\sqrt{3}}}{\frac{1}{\omega C} \cdot e^{-\frac{j\pi}{2}}} = \frac{400\,\mathrm{V} \cdot \omega C}{\sqrt{3}} \cdot e^{\frac{j\pi}{2}} \\[4pt] \varphi_I = \frac{\pi}{2} \\[4pt] \varphi = \varphi_U - \varphi_I = 0 - \frac{\pi}{2} = -\frac{\pi}{2} \end{gathered} \]

The capacitor adds a current at the grid terminals with a negative phase between voltage and current. The (motor) load has a positive phase between voltage and current. We can set the current into the capacitors so that the phases compensate each other overall. For this, let us look at the node equation for the line current I1 as an example:

Load and reactive power compensation at the grid connection: the grid current I1 splits into I1L and I1B
Netzanschluss = grid connection · Last = load
\[ I_1 \text{ (grid current)} = I_{1L} \text{ (into the load)} + I_{1B} \text{ (into the capacitor)} \]

\[ \begin{gathered} \text{From the example above:} \\[2pt] I_{1L} = \frac{U_1}{Z_1} = \frac{\frac{400\,\mathrm{V}}{\sqrt{3}}}{\sqrt{2} \cdot e^{j\frac{\pi}{4}}} = 163.3\,\mathrm{A} \cdot e^{-j\frac{\pi}{4}} \\[4pt] \cos(\varphi_{IL}) = 0.71 \text{ (ind)} \end{gathered} \]

\[ \begin{gathered} \text{Compensation network:} \\[2pt] I_{1B} = \frac{U_1}{Z_C} = \frac{\frac{400\,\mathrm{V}}{\sqrt{3}}}{\frac{1}{\omega C} \cdot e^{-j\frac{\pi}{2}}} = \frac{400\,\mathrm{V} \cdot \omega C}{\sqrt{3}} \cdot e^{j\frac{\pi}{2}} \end{gathered} \]

The challenge is to get cos(φ) up to at least 0.95. For this, the reactive current component of the load must be reduced by the reactive power compensation. Let us first calculate the active current and the reactive current at the load:

\[ \begin{gathered} \mathrm{Im}\{I_{1L}\} = \mathrm{Im}\left\{163.3\,\mathrm{A} \cdot e^{-j\frac{\pi}{4}}\right\} = 163.3\,\mathrm{A} \cdot \sin\left(-\frac{\pi}{4}\right) = -115.5\,\mathrm{A} \\[4pt] \mathrm{Re}\{I_{1L}\} = \mathrm{Re}\left\{163.3\,\mathrm{A} \cdot e^{-j\frac{\pi}{4}}\right\} = 163.3\,\mathrm{A} \cdot \cos\left(-\frac{\pi}{4}\right) = 115.5\,\mathrm{A} \\[4pt] \varphi_{IL} = -\frac{\pi}{4} \end{gathered} \]
Phasor of the load current I1L with real and imaginary part in the circle of radius 163.3 A

We change the reactive current, not the active current. The active current must remain unchanged in reactive power compensation. With cos(φ) = 0.95 and unchanged active current, the reactive current may take at most the following value:

\[ \begin{gathered} \text{Calculating the permissible phase shift at conductor 1:} \\[2pt] \text{Problem at the load: } \cos(\varphi_L) = 0.71 \text{ (ind)} \rightarrow \varphi_L = 45^\circ,\; \varphi_{IL} = -45^\circ \\[4pt] \text{Goal in the grid at } L_1\text{: } \cos(\varphi_1) = 0.95 \rightarrow \varphi_1 = \arccos(0.95) = 18^\circ,\; \varphi_{I1} = -18^\circ \end{gathered} \]

\[ \begin{gathered} \text{Calculating the maximum current } I_1 \text{ at the grid connection:} \\[2pt] \text{unchanged active current into the load: } \mathrm{Re}\{I_{1L}\} = 115.5\,\mathrm{A} \\[2pt] \text{permissible reactive current into the load leading to } \cos(\varphi_1) = 0.95\text{:} \\[4pt] \tan(\varphi_1) = \tan(-18^\circ) = \frac{\mathrm{Im}\{I_{1L}\}}{\mathrm{Re}\{I_{1L}\}} = -0.33 \\[4pt] \text{Rearranged: } \mathrm{Im}\{I_1\}_{\mathrm{Max}} = \mathrm{Re}\{I_{1L}\} \cdot \tan(\varphi_1) = 115.5\,\mathrm{A} \cdot (-0.33) = -38.12\,\mathrm{A} \\[2pt] \text{At the load, with an active current of } 115.5\,\mathrm{A}\text{, a reactive current of } -38.12\,\mathrm{A} \text{ leads to } \cos(\varphi_1) = 0.95 \end{gathered} \]

\[ \begin{gathered} \text{Required reactive current into the capacitor (node rule):} \\[2pt] \mathrm{Im}\{I_{1B}\} = \mathrm{Im}\{I_1\}_{\mathrm{Max}} - \mathrm{Im}\{I_{1L}\} = -38.12\,\mathrm{A} - (-115.5\,\mathrm{A}) = 77.39\,\mathrm{A} \\[4pt] \text{Capacitor current (blue): } I_{1B} = 77.39\,\mathrm{A} \cdot e^{j\frac{\pi}{2}} = j77.39\,\mathrm{A} \end{gathered} \]
Phasors of load current I1L, capacitor current I1B and compensated grid current I1
\[ \begin{gathered} \text{Thus achieved: } \varphi_{I1} = -18^\circ,\; \cos(\varphi_1) = 0.95 \text{ (ind)} \end{gathered} \]

\[ \begin{gathered} \text{Calculating the capacitance required for this current:} \\[2pt] \text{Grid frequency } f = 50\,\mathrm{Hz} \rightarrow \omega = 2\pi f = 314.16\,\frac{1}{\mathrm{s}} \\[4pt] I_{1B} = \frac{U_1}{Z_C} = \frac{U_1}{\frac{1}{j\omega C}} = j\omega C U_1 \\[6pt] C = \frac{I_{1B}}{j\omega U_1} = \frac{j77.39\,\mathrm{A}}{j314.16\,\frac{1}{\mathrm{s}} \cdot \frac{400\,\mathrm{V}}{\sqrt{3}}} = 1.07\,\mathrm{mF} \end{gathered} \]

Simulation

Of course, the numerical values from the example do not apply in general. But the method for calculating the capacitor does. The following general formulas apply:

\[ \begin{gathered} \tan(\varphi) = \frac{\mathrm{Im}\{X\}}{\mathrm{Re}\{X\}}\text{, applies to currents, voltages and powers} \\[4pt] \text{General phase equation: } \varphi = \varphi_U - \varphi_I \\[4pt] \varphi_U = 0 \text{ applies only to phase 1 in star connection} \end{gathered} \]

\[ \begin{gathered} \cos(\varphi) = \frac{P}{|S|} \\[4pt] \text{For currents:} \\[2pt] \tan(\varphi_I) = \frac{\mathrm{Im}\{I\}}{\mathrm{Re}\{I\}} \\[4pt] \cos(\varphi_I) = \frac{\mathrm{Re}\{I\}}{I} \\[4pt] \sin(\varphi_I) = \frac{\mathrm{Im}\{I\}}{I} \end{gathered} \]

\[ \begin{gathered} \omega = 2\pi f \text{ with } f = 50\,\mathrm{Hz} \text{ for three-phase current} \\[4pt] I = \frac{U}{Z},\; Z_R = R,\; Z_L = j\omega L,\; Z_C = \frac{1}{j\omega C} = -j\frac{1}{\omega C} \end{gathered} \]

Download course as PDF

The PDF contains all pages of the course. Interactive content is only available on the website.